RAILROAD-1-EP

|
|
DIGITAL COMPLEX PROTECTION FOR SINGLE PHASE
RAILROAD SYSTEM |
|
RAILROAD-1-EP digital complex protection has
been specially designed for single phase electrified railroad system. It
contains a distance relay with 5 independently programmable quadrilateral
zones, a fault locator, an autoreclosing system, and a thermal overload
relay. |
|
Main Features |
|
- Full scheme distance relay with 5 zones
- All parameters of the zones can be set independently
- 2 forward zones, 1 reverse zone, 2 programmable to be forward or reverse
- All zones have quadrilateral characteristics
- Two different measuring algorithms:
- the first zone has a very fast three point measuring algorithm
which is insensitive to CT saturation
- the other 4 zones use an algorithm with Fourier filtering
- Polarising for directional detection without dead zone at close-up
faults
- Instantaneous definitive trip at switch-on-to-fault
- Signal from VT midget CB is used for VT circuit supervision
- Built-in automatic fault locator
- Operating time: 25 ± 5 ms
- One shot auto-reclosing
- Each impedance zone from 1 to 4 can be independently set to start
or block auto-reclose
- Operation of zone 5 (always reverse) generates definite trip
- AR function can be blocked or enabled with parameter or hardware input
or via user-defined logical equation
- Complete thermal overload relay for best protection against line overheating
- Separate current input for thermal overload relay
- Thermal overload relay has pre-alarm and trip stages
- Thermal overload relay takes the effect of previous heating into consideration
(heating and cooling processes)
- PROTLOG powerful logic with 8 user definable logic equations. User
can add breaker-failure and other functions to the basic set. It can
also eliminate usage of auxiliary contacts and time relays
- Built-in software matrix to parameterise the functions of output contacts
and indicating LEDs
- Built-in self test function with dc supply check, trip/close circuit
supervision and Watch Dog
- One serial communication direction with two ports: (selectable with
a parameter)
- an isolated RS 232 connector on the front plate
- a fiber optic connector on the rear plate
- Two types of event recording:
- event log for storing collected data of the last 50 protection
operations
- event sequence recorder with 1 ms resolution for 300 events
- 16 isolated optical coupled binary inputs
- 8 output contacts with user-defined functions. Each can be NO or NC
- 6 programmable indicating LEDs
- Man-machine communication via external PC or built-in LCD display
- Battery backed-up RAM to store events and running real time clock
- Clock synchronisation with external binary input or on serial link
|
|
Technical Data |
|
Rated secondary current, In
|
1 A ili 5 A |
Rated secondary line voltage, Un |
100 V, 110 V ili 200 V |
Rated frequency |
50 Hz |
Overload capacity, in voltage circuits, continuous
Overload capacity, in current circuits, continuous
1 s |
1,2xUn
2xIn
100xIn (In=1 A), 50xIn (In=5 A) |
Dynamic current limit |
100xIn |
Accuracy of digital impedance relays (> 50 % In) |
± 5% |
Accuracy of digital current relays (> 50 % In) |
± 2% |
Accuracy of digital timer |
± 3 ms (10 ms steps)
± 12 ms (1s steps) |
Impedance stages, hysteresis |
15% |
Reset ratio of current relays |
95% |
Optical isolated inputs |
16 pcs, 220V DC |
Output relays |
8 pcs printrelays |
Output relay contact type |
programmable by matrix: 8 pcs |
Output contacts ratings,
rated switching voltage
continuous load current
switching on current
breaking current at 220 V dc,
pure conductive circuit
L/R = 40 ms
option: L/R = 40 ms |
250 V
8 A
16 A
0,25 A
0,14 A
4 A |
Auxiliary dc battery voltage (the same supply unit)
voltage tolerance
|
220 V or 110 V
88 V to 310 V |
Permissive ambient temperature |
0o to 50o C |
Insulation test (IEC 255) |
2 kV, 50 Hz
5 kV, 1.2/50 µs |
Disturbance test (IEC 255) |
2.5 kV, 1 MHz |
Electrostatic discharge test (ESD; IEC 801-2) |
8 kV |
Burst test, (IEC 801-4) |
2 kV |
Electromagnetic (radiofrequency) interference test |
IEC 801-3 |
|
|
Design, size |
|
An EuroProt device is always rack-mounted type.
One of the design form is suitable to mount directly into a standard 19"
inch cabinet frame. The other designs are panel mounted devices with raised-hinged
or flush mounted forms. Outline size of a 19 inch cabinet frame mounted
device and a panel mounted device with flush mounted form is as follows.
Design
|
Width
|
Height
|
Depth
|
Rack mounting
|
483 mm
|
132,5 mm
|
201 mm
|
Panel mounting
|
490 mm
|
250 mm
|
250 mm
|
Terminal type at panel mounted design is as follows (terminal are placed
onlydown).
Switchable: 02 to 20 terminals, WTL6/1 Weidmuller
Not switchable: 21 to 73 terminals, WDU 2,5 Weidmuller,
Weight 8 kg.
|
|
Optional Functions |
|
- Digital fault recorder with 80 sec recording time
- RTU card with IEC 870-5-101, 870-5-103, MODBUS protocols and complete
RTU functions
- Additional binary input and output contact cards for RTU tasks
- Graphic LCD display (320x240 pixels) on front plate for displaying
measured values and one-line scheme
|
|
|