|
IHS-1T
|
 |
DIRECTIONAL
EARTH-FAULT RELAY |
|
Application |
|
The IHS 1T devlce is intended for directional earth-fault protection
of networks with isolated, compensated, low resistance earthed and directly
earthed neutral.
Information on homopolar current can be obtained from either a parallel
connection of three current measuring transformers or from a cable transformer.
The use of a cable transformer offers more sensitive current setting of
the directional earth-fault protection.
|
|
Description |
|
The directional earth-fault relay receives information on voltage from
a voltage measuring transformer while information on current is received
from a current measuring transformer.
According to the block diagram in fig. 1, information on current goes
to the current comparator I > in which the required pick-up current
setting is effected (in the range of 0,0 1 A to 0,6 A) .
Information on current direction is formed through observing both voltage
and current zero crossings. The zero crossing of voltage triggers a monostable
multivibrator circuit which generates a square wave pulse at its output
of duration b, adjustable from 0,55 ms to 10
ms. The falling edge of the square wave pulse having duration b
triggers the next monostable multivibrator circuit which generates a square
wave pulse of duration h= 10 ms.
If the instant of zero crossing of current falls within the interval h,
that means that the current Iaggs behind the voltage for the time equal
to at least b. Considering that the Iagging
time corresponds to phase shift, the duration b
is calibrated in degrees directly (and can be set from 10° to 180°). A
graphical interpretation is presented in fig. 2. With voltage and current
measuring transformers connected as in fig. 1, the angle b
can be defined as the angle existing between voltage and the "nearer"
limit of the relay pick-up zone (having the "width" of 10 ms,
resp. 180°). It is therefore possible, by selecting b,
to select an arbitrary position of the relay pick-up semi-plane in the
plane Uo, Io and thus to match the relay optimally to network conditons.
In the example on fig. 2, it is visible that fault current Io1 falls within
the relay pick-up zone.
|
|
Features |
|
The IHS-1T relay is made with high quality and reliable semiconductor
components. Static construction has offered high reliability, accuracy
and sensitivity. The sensitivity does not depend on the angle between
current and voltage. The relay operation is normal already at 0, 1% Un
and 10 mA earth-fault current.
The choice of pick-up current settings and of pick-up zone positions of
the relay is possible within wide limits by mepns of the setting elements
on the relay front panel. The recommended values for b
angle settings are:
-in network with isolated neutral. b = 10°
to 50° .
-in network with compensated neutral b= 50°
to 80°
|
|
SPECIFICATIONS |
|
Rated voltage
|
100V; (110V); 50Hz
|
Setting range |
|
I>
|
(0,01-0,6)A
|
t>
|
(0,2-6)s
|
b |
10ošš - 180o
|
Accuracy of scales |
|
I> |
5%
|
t> |
5% for t>1s
|
|
50 ms for t<1s
|
b |
5o
|
Sensitivity voltage treshold |
10V
|
Power drain |
|
from the current path |
0,5 VA
|
from the voltage path |
0,3 VA
|
from the auxiliary source of supply
|
|
at 110V DC |
7W
|
at 220V DC |
14W
|
Auxiliary supply voltage from the storage
battery or regulated supply source |
110V DC, 220V DC; -15%+10%
|
Current overload |
|
continuous |
10A
|
6s |
50A
|
3x1s |
150A
|
Contacts |
|
Maximum voltage |
250V
|
Continuous current |
5A
|
Current at make |
10A
|
Breaking capacity |
|
for cosj = 1 |
1000VA
|
for DC at L/R=40ms. |
20W
|
Ambient temperature |
-10oC to +50oC
|
Test voltage |
2kV, 50Hz, 1 min.
|
Mass |
1,9 kg approx.
|
Dimensions |
as on fig. 3
|
|
|
How to order |
|
- type of unit
- auxiliary voltage
For all inquiries please contact the manufacturer.
Subject to change without prior notice.
|
|
|