|
DTVA-EP
|
|
DIGITAL DISTANCE PROTECTION
WITH AUTOMATIC RECLOSING DEVICE |
|
The digital distance protection with automatic
reclosing device, type DTVA-EP is part of device family named EuroProt.
This short description contains special data of this type. General and common
features of EuroProt family can be found in the EuroProt system information
sheet. Accordingly it is proposed to study both this short description and
system information sheet too, in order to understand the device entirely.
|
|
|
|
Application field |
|
The DTVA-EP type digital distance protection
completed with one and three phase three shot automatic reclosing device
and automatic fault locator may be applied as a selective phase and earth
fault protection and automatic reclosing device of an overhead line or a
cable in a high voltage effectively earthed meshed network. |
|
Main features |
|
- electronic device with module system,controlled by microprocessors
set-up from IC's placed on plugged PCB's
- five stages with impedance polygon characteristics
- 4th and 5th stage may be set to forward and backward direction
- stages measure by equation of UL / IL at three
phase and phase-to-phase faults, and by UF / (IF
+ a3I0) at phase to earth faults
- impedance detection with three point measuring principle which is
insensitive to CT saturation
- directional detection without dead zone on close-in-fault
- instantaneous definitive trip on manual close-to-fault
- three phase overcurrent relay with independent time delaying, it may
be set with PROTLOG operation equation to be active on tripping of VT
midget CB only
- sensitive earth fault overcurrent protection with zero sequence current
detection
- one and three phase automatic recloser (OR, TR)
- one fast reclosing cycle (FR)
- two slow reclosing cycles (1SR, 2SR)
- step acceleration [t(Z2<) = 0]
- step acceleration or selective trip at first trip, after FR, after
1 SR and at definitive trip
- step acceleration may be blocked on three phase trip
- each reclosing cycle may be set to OR or TR
- each reclosing cycle may be set to be active or blocked
- automatic fault locator displaying the last fault data
- operation time is 25 ± 5 ms
- digital design with independent A/D converter, separate digital signal
processor (DSP) and separate main processor
- built-in self check function with dc supply check, trip/close circuit
check and Watch Dog, with healthy-to-work failure signal and message
on LCD display
- external communication connectors on front plate for RS 232, on back
plate for optical fibre cable
- event log for storing 50 events, event sequence recorder with 1ms
resolution for 300 events
- 16 optical coupler inputs
- 20 output contacts, 8 of which have fixed operation, 12 of which may
be freely programmed by matrix
- type of last 12 contacts may be required on ordering (NO or NC)
- intelligent digital function matrix
- operation equations of PROTLOG system to be freely chosen with 18
outputs and 32 inputs
- 5 equations of which is matrix row, i.e. to operate contacts, handling
(to set protection, to display messages, to
inquire event recorder data, etc.) by external PC, or by built-in man-machine
connection
- on-line screen display may be seen on an external PC to be easy commissioning
and testing, to get real time current values
- real time clock handling with the aid of a RAM with battery, which
may be synchronised through an optical fibre
cable by external PC or through a digital optical coupler
|
Working principle |
|
The current and voltage inputs go through inductive
auxiliary transformers and low pass filters to the multiplexer and the sample/hold
circuit which gets sample in each 0,5 ms. Signals of an NO converter go
through high speed series bus to the central unit and to the fault recorder
if it was ordered as an option. In the central unit, a digital signal processor
(DSP) makes necessary arithmetical operations with high speed. A central
processor carries out the time delaying and logical functions, and holds
interconnections with the optical coupler inputs and the output relay drivers.
The overcurrent stages (3Io>t, I>t) detect current with average measurement.
The operation conditions of the phase OC stage may be chosen by programming
of the relevant PROTLOG equations. It is advisable to programmed a condition
the phase OC stage can operate only if the midget VT CB trips, since then
the impedance stages are blocked. The phase OC stage blocks the automatic
reclosing, trips always definitely but in one or three phases according
to the setting of definite trip parameter.
The distance protection has got three stages with forward direction and
two stages with forward as well as backward direction arbitrary settable.
The first stage does not have time delaying, but time delaying of the others
may be set independently.
The five stages of the distance protection are blocked by the VT midget
CB trip.
The first and second stages of the distance protection start the automatic
reclosing device, the third, fourth and fifth stages give definite trip.
The time versus distance characteristic of the five impedance stages is
seen in Figure 1. , the characteristics in the impedance plane are in Figure
2.
The single-phase-to-earth and two-phase-to-earth faults is chosen by a zero
sequence current relay (3Io) having a biased characteristic.

The distance protection is able to receive permissive overreach and underreach
transfer trip command from the distance protection placed on the other side
of the protected line. The command overrides the second stage timer [t(Z2<)
= 0].
On close-in-fault, the protection remembers the voltage before the fault.
This feature gives a direction detection without dead zone.
On close-to-fault, the fact of whole voltage collapse (neither before nor
under the fault) determines the close-to-fault event, so if there is current
detection in the same time as well, the protection trips instantaneously
and definitely.
The distance protection contains a built-in three shot automatic reclosing
device with one and three phase reclosing (OR and TR) which is suitable
to apply on an effectively earthed network.
If one phase reclosing is set, the protection trips the faulty phase of
the CB only on single-phase-to-earth fault, but all the three phase will
be tripped on two-phase, two-phase-to-earth and three phase fault. If three
phase reclosing is set only, on any fault, the protection trips all the
three phase.
The three shot automatic recloser consists one fast reclosing cycle (FR),
and two slow reclosing cycles (1SR and 2SR).
Only the first and second stages of distance protection start the automatic
reclosing. Similarly, both stages may be set that the protection trips the
CB in one phase only on single-phase-to-earth fault. This parameter setting
may be made at first fault (if there is FR or 1-2SR), at a fault after the
FR (if there is 1-2SR), at a fault after 1 SR (if there is 2SR), and at
the definitive trip.
The first trip of the distance protection may be set to be selective or
step acceleration. The same may be set at a trip after FR, after 1 SR and
at the definite trip. The step acceleration means the second stage operates
without time delaying [t(Z2<) = 0].
PROTLOG logical system is built into the distance protection by the PROTECTA
Co. Ltd. The essence of the system is the user can create equations of Boole
algebra for the input variables. The equations operate the output variables
if the equations are realised. 32 input signals and 19 output signals are
used in the PROTLOG system built in the protection. The number of the output
signals determines the highest number of equations to be created. |
|
Technical data |
|
Rated secondary current, In |
1 A or 5 A |
Rated secondary voltage (line), Un |
100 V or 200 V |
Rated frequency |
50 Hz
|
Overload capacity,
voltage circuit, thermal, continuous
current circuit, thermal, continuous
1 s |
1,3xUn
4xIn
100xIn (In=1 A), 50xIn (In=5 A) |
Dynamic current limit |
100xIn |
Accuracy, impedance relays, (over 50% In)
Accuracy, current relays, ( over 50 % In)
Accuracy, timers |
± 5%
± 2%
± 3 ms (10 ms steps)
± 12 ms (1 s steps) |
Hysteresis, impedance stages |
15% |
Reset ratio, current relays |
95% |
Binary inputs opto-coupled
|
16 pcs, +8 as an option |
Output relay contacts
|
20 pcs |
Type of contacts: with fixed connection: R 1TRIP, S
1TRIP, T 1TRIP, R 2TRIP, S 2TRIP, T2TRIP (all NO), healthy-to-work
signal (NC)
programmed with matrix: 12 pcs, NO in factory, but changed on ordering |
Output contacts, electrical data:
rated switching voltage
continuous load current
making current
DC breaking capability at 220 V,
at pure conductive load
at load ofL/R =40 ms |
250 V
8 A
16 A
0,25 A
0,14 A |
Auxiliary DC voltage
voltage tolerance |
220 V or 110 V
88 V to 310 V |
Permissible ambient temperature |
0o to 50o C |
Insulation test (IEC 255) |
2 kV, 50 Hz
5 kV, 1.2/50 µs |
Disturbance test (IEC 255) |
2.5 kV, 1 MHz |
Electrostatic discharge test (ESD; IEC 801-2) |
8 kV |
Burst test, (IEC 801-4) |
2 kV |
Setting ranges: |
Impedance stages on real axis, R1
on imaginary axis, X1 |
(0-10000)*(*10*Cu*Ci) mOhm
step 10*(*10*Cu*Ci) mOhm(0-10000)*(*10*Cu*Ci) mOhm
step 10*(*10*Cu*Ci) mOhm |
Setting of directional relay, angular coefficient on
X axis, -R1/X1
angular coefficient on R axis, -X1/R1 |
0-50%, step 1%
0-50%, step 1% |
Z4, direction |
1/0 (1=forward, 0=backward) |
Z5, direction |
1/0 (1=forward, 0=backward) |
Line impedance for fault locator Xn(line)(*10*Cu*Ci) |
100-5000 mOhm, step 10 mOhm |
3I0 zero sequence current mixing, a |
0-100%, step 2% |
3I0 fault detector, basic sensitivity |
10-50%, step 1% |
3I0 fault detector, biasing |
5-30%, step 1% |
The factors found in above parameter equations:
(*10*Cu*Ci)=Un / (10*In)
|
CT rated current |
50-1500 A, step 25 A |
Phase O/C relay, I>/In (operates VT midget CB trip
only) |
30-2500%, step 5% |
Voltage stage, U<>/Un |
0-100%, step 2% |
Voltage stage type, U<> |
0/1 (0=overvoltage, 1=undervoltage) |
Impedance stage timer (except first stage), t |
0-60000 ms, step 10 ms |
Phase OC timer, t(I>) |
0-60000 ms, step 10 ms |
Voltage stage timer, t(U<>) |
0-60000 ms, step 10 ms |
Healthy-to-Work failure Signal timer, t(fail) |
0-600 s, step 1 s |
Timer of equtions, t |
0-60000 ms, step 10 ms |
FR i HR dead time |
0-60000 ms, step 10 ms |
SR dead time |
0-600 s, step 1 s |
External communication |
RS 232/optical fibre cable |
Optical cable operating mode |
radial or loop |
External communication speed (BaudRate) |
150 to 19200, step 2x |
Daily automatic self-check time |
0 to 23 h 59 min, step 1 min |
Automatic self-check block |
setting to 60 min |
No. of devices within a system |
0-254 |
No. of devices within a substation
|
0-254 |
|
|
Design, size |
|
An EuroProt device is always rack mounting.
It has two design forms. One of the form is suitable to mount into a standard
19" inch cabinet frame, this form is also able to mount directly to
a relay panel with flash mounted form. The other form is a relay panel mounted
device with raised-hinged form Its size depends on the chosen form. |
|
Outline size of a 19 inch cabinet frame mounted device
Width
|
Height
|
Depth
|
483 mm
|
132,5 mm
|
201 mm
|
Outline size of panel mounted device
Width
|
Height
|
Depth
|
490 mm
|
250 mm
|
250 mm
|
Weight: 8 kg.
|
|
Options |
|
Some especial units as built-in parts may be required to be delivered
with the distance protection as follows:
- digital fault recorder (see separate information sheet)
- longitudinal differential protection
- SCADA connection (see EuroProt system information sheet)
- relay contacts with 4 A breaking capability
- toroidal type CT input PCB
- 8 pcs binary inputs for the PROTLOG operating equations
|
|
Data to be ordered |
|
- Protection type [DTVA-EP]
- Protection case type [19 inch cabinet frame mounted device, panel
mounted device with flash mounted form, panel mounted device with raised-hinged
form]
- Rated current [1 A, 5 A]
- Rated voltage [ 100 V, 200 V]
- Output relay contact types [if deviates from the Technical Data]
- Options [if required]
|
|
|