Input currents of the device through inductive
auxiliary C.T. and analogue low pass filter go to the multiplexer, and the
S/H, where each phase current and the zero sequence current will be sampled
by 0.5 ms, and each overcurrent stage is separately applied to each input
currents.
The time delaying of the eight overcurrent relais may be independently
set. The high and low setting stages and the accelerated stages may also
be separately set.
The Live Line Working (LLW) needs a particular operational condition
which means in the protection to trip with preset time delaying if Uo
has appeared.
A three shot reclosing device is built in, these are a fast shot (FR),
and two slow shot (1st SR, 2nd SR). Each shot may be made active and blocked.
Each trip may be programmed to accelerated and delayed one, but the definite
trip is always selective if there was not selective trip before it. The
reclaim time of reclosing device is 5 s, fixed.
Two setting packs may be set on the device, in which all the settig values
except the dead times may be preprogrammed in two variations so the setting
of automatic device can be easily changed by hand or by remote control.
If the back up protection trips, the reclosing device gives a definite
trip, and the recloser is blocked for the reclaim time.
If no fault after reclosing, the reclosing device goes back to the basic
state.
The reclosing device may be controlled by blocking or permissig command.
The device remembers to the blocking condition after supply voltage loss,
as well.
If the reclosing device is blocked, the detection of relais I>>,
I>, 3Io>> and 3Io> will trip with selective delaying.
Control commands can be put to the eight optical coupler inputs. Six
of them fixed command (manual closing, reclosing blocked, reclosing permitted,
LLW switch, reclosing stopped, reclosig device external start e.g. from
pilot wire protection) while two command may be programmed.
Logical interconnection between the protection units as well as timers,
and the output relais may be programmed by a software matrix.
A continuous and a periodical monitoring system is buit into the device.
The continuous monitoring system checks the supply voltage presence, the
healthness of the basic current circuits and the control circuits. The
periodical monitoring system starts daily in a preset time, and when it
is started by hand by the aid of the Control menu point of the Parametring
basic menu. Both monitoring system gives alarm and automatic message appears
on the LCD display when a fault is found.
The protection workings will be stored by an event log with 50 events
memory, and by an event sequence recorder with 1 ms resolution and 300
events memory. The event log and the event sequence recorder may be read
through series line.
The device can be completed with an entirely independent, self feeding
overcurrent back up protection of type KZT. The back up protection is
a classical electronic device set up with I.C.'s.
|