DT 23-d; DT 33-d

DIFFERENTIAL RELAYS
 
Application
 

The differential relays DT 23-d and DT 33-d are primarily intended for the protection of power transformers against faults within the protected zone (two-phase and three-phase short circuits, inter-winding faults in transformers, earth-faults, double phase-to-earth faults for transformers with earthed neutral.
The differential protection device (differential relay) represents a basic device in the protection of power transformers (with or without tap changing facility) and can be also applied for the protection of generator-transformer units and high power rating generators.
The protected zone is determined by the location of current measuring transformers both in front of, and behind the protected transformer, and includes the transformer terminals and current transformer connections as well.
The Iine of differential protection devices type DT consists of:

DT 23-d -the device for differential protection of two- winding transformers;
DT 33-d -the device for differential protection of three- winding transformers.

 
Description
 

The principle of operation of the device for differential protection, type DT will be demonstrated on an example of the device for differential protection of two-winding transformers. The single-line block diagram is indicated In fig. 1.
The device comprises in each phase:


-differential transformer (DT)
-restrain ing transformer (ST)
-locking assembly
-electronic assembly

Under normal operating conditions, current I1 -I2 passes through the differential transformer circuit, and current (I1 + I2 )/2 through the restraining transformer circuit. Current (I1) is proportional to the primary current, and current (I2) to the secondary current of the protected transformer. The proportionality coefficients have been so selected that under normal operating conditions I1 = I2 , so there will be no current running through the differential transformer. The current running hereby through the restraining transformer is I1; at the comparator circuit in- put in the electronic assembly, there exists a signal which prevents comparator activation, thus the differential protection device will not operate.
The device for differential protection is so designed that no operation shall take place in case of short circuits outside the protected zone. However, any fault occuring within the protected zone reduces the effect of the restraining current, and thus i mproves the device sensitivity to such types of faults.
In the case of short circuits within the protected zone (and in the case that the transformer lower voltage side is connected onto other power sources in the network) , there runs a sum of currents I1 and I2 through the differential transformer circuit, and through the restraining transformer circuit their difference; at the comparator circuit input there exists only the signal which activates the comparator, which results in practically instantaneous operation of the differential protection device. Due to magnetizing currents and errors in the current and interposed transformers ratios (specially if tapchanging equipment is present) a certain amount of debalance current usually flows through the differential transformer. Consequently, the lowest differential protection setting is so selected as to allow for the protection of power transformers with tap-changing facilltys within the limits of ± 15% Un.
When a power transformer is energized, particularly if its secondary is at no-load, a very high magnetizing inrush current (in an amount up to 10 In) can flow through its primary winding, which causes current I1 in the input circuit of the differential protection device. Considering that current I2 is hereby zero, it follovvs that the entire input current I1 is differential current, thus operation of the differential protection device would result. In order to prevent such unwonted operation, a locking assembly is included in the structure of the differential protection device, which determines on the basis of the differential current harmonic contents (second harmonic) whether magnetizing current or fault current is in question, and cansequently forbids or permits the differential protection device to respond.
The operating characteristics of the differential protection device at 20% In setting is indicated in fig. 2,. where Id stands for dIfferential current, and Is for restraining current.
The area above knee-shaped operating cahacteristic represents the operating zone, and the area below it the in sensitivity zone of the differential protection device.

According to figs. 1. and 3. it follows that each phase of the differential protection device operates quite indepen- dently, and that the only blocks common for all three phases are the electromechanical actuating relay and the comparator of high differential currents Id >> .
Information on restraining and differential current are fed to the summing block, and if their proportion is such as to activate the comparator circuit, the differential protection device will be operated (the actuating relay contacts close). In that case the comparator circuit also generates an electric signal required to operate the signalling module, if signalling of faulty phase is required. The signalling module, when operated by the comparator output signal, energizes an indicating lamp in the appropriate phase, indicating thus that the device has operated and identifies tile faulty phase. Resetting of the signalling module (to turn out indicating lamp) is performed by depressing button K. By removing a jumper across the terminals 26 and 27 (fig. 3) it is possible to effect remote resetting of the signalling on the differential protection device. However, no signalling resetting is possible if, for any reason, the protected object has not been cut-out. If high differential current occurs as a consequence of magnetizing current at the power transformer energisation, the locking assembly locks the comparator circuit operation, thus-preventing faulty operation of the device. In case of very high differential currents occuring (in excess of the amount set on the comparator Id >>, the device will be activated, without regard to the amount of the restraining current and differential current harmonic contents.
Inputs A1, C1, A2, C2, A3, C3 represent connections of the block strcture indicated in fig. 1 (for phase B only) with corresponding blocks of the phases A and C.
The devices for differential protection are sol id state units (static construction). Internal current transformers at the input and auxiliary relays of fairly high breaking capacity at the output, provide for a galvanic isolation of the electronic circuitry of the device from the power circuits.

The device is housed in a standard case for surface mounting (see the dimensions i n fig. 6) .The front plate (under a glazed cover) bears the functional diagram with the connection diagram (fig. 3), operation setting elements (jumpers) and indicating lamps with associated resetting button. The top terminals (arranged also under the cover) are equipped with jumpers (across the terminals 15 and 17; 19 and 21; 23 and 25) which enable simple checking of proper connection of the interposed transformers and measurement of current through the differential transformer in operation.
Standard interposed transformers are used with the DT type relays for differential protection. The choice of interposed transformers and the type of their connection are determined by the type of connection of the protected object, and can be made according to table 1 and fig. 5.

 
Features
 
The differential protection devices type DT are of static construction. They are made with high quality and highly reliable integrated circuits, thus high reliability, accuracy, speed of operation, and minimum power drain in the measuring circuit are achieved. The devices are not susceptible to mounting position, vibrations and shocks.
The design of the differential protection device provides for:

-full stability with respect to faults occuring outside the protected zone
-stabil ity of operating characteristics even incase of assymetrical failures (a separate differential relay for each phase)
-high sensitivity to faults within the protected zone
-intensitivity to supply voltage changes within wide limits and to ambient condition changes
-visual light indication of faulty phase (up on request)
-resetting facility of signalling, locally or remotely.
 
SPECIFICATION
Rated current
5A; 1A
Rated frequency
50Hz
Setting range (in steps)
20%, 30%, 40% and 50% In
Comparator Id>> setting
standard
20 In
on request
8 In; 12In; 16In
Overload capacity
2 In continuosly
20 In, 20s
100In, 0,5 s
Dinamic current
200 In (peak)
Pick-up time at 0,2 In setting
at Id = 2 In 60 ms approx.
Minimum pick-up time
20 ms approx.
power drain per phase at
in normal operation
In=5A
(restraining circuit)
0,2 approx.
under-fault conditions
(differential circuit)
0,4 VA approx.
power drain from the source

 

of auxiliary supply
at 110V 14,3 W approx.
at 220V 29W approx.
Auxiliary voltage from a storage battery or regulated power supply source
110V D.C. or 220V D.C.
Output relay contacts
maximum voltage
250V
continuous current
5A
current at make
10A
Breaking capacity at cosj = 1
1000VA
at D.C. at L/R=40 ms
20 W
Ambient temperature
-10oCšš + 50oC
Test voltage
2 kV; 50Hz; 1 min.
Type of signalling
visual, 1 LED diode per phase
Mass
6,8 kg
Dimensions
as in fig. 6.
 
How to order
 
  • type of unit
  • rated current
  • auxiliary voltage

For all inquiries please contact the manufacturer.

Subject to changr without prior notice.