Rated secondary current, In
Rated zero sequence current, Ino
(other value can be given when ordering)
|
1 A, or 5 A
0.1 A, 1 A, 5 A |
Primary current of feeding C.T. |
50 to 1500 A, step 25 A |
Primary current ratio, zero sequence C.T.
in case of toroidal type C.T. |
150/5 A |
Rated frequency
|
50 Hz (60 Hz on request) |
Overload capacity, in current circuits,
continuous
1 s |
4×In
100×In (if In = 1 A)
50×In (if In = 5 A) |
Dynamic current limit |
100×In |
Setting ranges: |
Motor rated current, In
in per cent of the main C.T. rated current, In
/ I |
30 to 120 %, step 2 % |
Idle operation minimum threshold current (fixed) |
IIDLE / In
= 15 % |
Phase fault O.C. relay starting current, I> / I
time delaying, t (I>) |
50 to 1500 %, step 10 %
0 to 60000 ms, step 10 ms |
Earth fault O.C. relay starting current, 3Io>
/ I
time delaying, t(3Io>) |
10 to 100 %, step 2 %
0 to 60000 ms, step 10 ms |
Motor rated temperature rising to its ambient
when the motor load is In rated current |
Qn = 10 to 100 °C, step 1 °C |
Overheating previous alarm signal setting value
in per cent to the motor rated temperature rising |
Qp / Qn = 60
to 160 %, step 2 % |
Thermal overloading (overheating) trip setting value
in per cent to the motor rated temperature rising |
Qt / Qn = 80 to 180 %, step 2 % |
Limit temperature rising to block the starting again
command in per cent to the motor rated temperature rising |
Qb / Qn = 60
to 160 %, 2 % |
Time constant for rotating motor temperature rising
and cooling |
TR = 2 to 200 min., step 1 min. |
Standing motor cooling time constant in per cent
to the time constant for rotating motor |
TC / TR (Tcool / Trise)
=
100 to 400 %, step 100 % |
Asymmetry protection starting value, fixed |
I2/In = 15 % |
Asymmetry protection inverse definite minimum time
relay, maximum time delaying at fixed starting current (I2
= 0.15×In) |
t as = 10 to 80 s, step 2 s |
Asymmetry protection inverse definite minimum time
relay, minimum time delaying at very high I2
current |
t asmin = 50 to 500 ms, step 50 ms |
Load loss protection starting current in per cent to
the motor rated current |
It < / In
= 30 to 60 %, step 5 % |
Load loss protection time delaying |
t(It) = 1 to 10 s, step 1 s |
Starting period setting value |
tst = 5 to 100 s, step 5 s |
Fault during starting period, setting current |
Ist / In = 200 to 800 %, 10 % |
At heavy starting setting, during the starting period,
the heating current
|
I2 / 2, fixed |
Bearing or rotor stalling prot. after starting period |
2xIn, if t > tst |
Accuracy, current relays (over 50 % In) |
± 2 % |
Accuracy, timers |
± 3 ms, at step of 10 ms
± 12 ms, at step of 1 s |
Current relays, resetting ratio |
95%, fixed |
External communication |
RS 232 or optical fibre cable |
External communication (BaudRate) |
150 to 19200 Baud, step 2 times |
Automatic daily self check, starting time |
0 to 23 hour 59 minute, step 1 minute |
Automatic daily self check, blocking |
setting to 60 minute |
No. of substation in a system |
0 to 253 |
No. of device in a substation |
0 to 253 |
Number of output relays |
8 pcs |
Output contacts ratings,
rated switching voltage
continuous load current
switching on current
breaking current at 220 V DC,
pure conductive circuit
L/R = 40 ms load
|
250 V
8 A
16 A
0.25 A
0.14 A |
Auxiliary DC voltage (the same supply unit)
voltage tolerance
optionally, on ordering
|
220 V, 110 V
88 to 310 V
48 V |
DC consumption, basic state
at working |
< 7 W
< 9 W |
Permissive ambient temperature |
0 °C to 50 °C |
Insulation test (IEC 255) |
2 kV, 50 Hz
5 kV, 1.2/50 ms |
Disturbance test (IEC 255) |
2.5 kV, 1 MHz |
Electrostatic discharge test (ESD) (IEC 801-2) |
8 kV |
Burst test (IEC 801-4) |
2 kV |