|
DGSZV-EP

|
|
DIGITAL GALVANIC LONGITUDINAL
DIFFERENTIAL PROTECTION |
|
The digital galvanic longitudinal differential
protection of type DGSZV-EP is part of device family named EuroProt. This
short description contains special data of this type. General and common
features of EuroProt family can be found in the EuroProt system information
sheet. Accordingly it is proposed to study both this short description and
system information sheet too, in order to understand the device entirely. |
|
|
|
Application field |
|
The DGSZV-EP type digital galvanic longitudinal differential protection
of can be applied in electric power generating plants, transmission and
distribution substations of the electric power system to quick and selectively
protect high or medium voltage lines or cables against phase or ground
faults.
There are basically three versions:
- a three phase version for effectively grounded networks
- a two phase device to protect medium voltage compensated or isolated
networks against phase faults
- in medium voltage resistance grounded or compensated network with
neutral resistor for increasing the earth fault current, against phase
and ground faults
The protection needs a single-phase, three wires, galvanic connection
between the devices of both ends of the line. The connection is continuously
supervised, in case of failure an alarm signal is generated, and disables
or submits a trip command, according to the parameter setting.
|
|
Main features |
|
The protection contains a differential measuring element of a percentage
bias characteristic with settable basic sensitivity (DI),
an overcurrent function measuring in two phases (I>(t) and I>>(t)),
four basic and two additional, free applicable timers (T1, T2).
The stages of the galvanic longitudinal differential protection and overcurrent
functions can be enabled independently of each other. The parameters for
the differential protection, the current and the voltage elements and
the timers can be set independently.
The length of the single phase, three line, galvanic connection between
the devices at both ends, in case of copper conductor may be maximum 10
km, the cross-section must be at least 1,5 mm2. The three phase
basic version of the device can be applied connected to two phases, or
two phases and Io as well.
The trip command can depend on undervoItage state. The phase selection
is decided by the under voltage function, but it is not absolutely necessary.
The characteristics with two knee points can be set as needed, the biasing
is made with the average of absolute value of currents at both ends.

The trip characteristics of the digital galvanic longitudinal
differential protection
The operating time of the differential protection is approx. 35 ms.
Software characteristics:
- built-in self-check functions
- digital event recorder for 50 events, and an event sequence recorder
with 1 ms time resolution for maximum 300 events
- analog event records with current data
- two additional timers (T1 and T2) in connection with the software
matrix
- the rows of the matrix (the relay-functions) can be latched
Hardware characteristics:
- numerical type, with own A/D converter and digital signal processor
(DSP) and separate main processor
- 8 opto-coupler inputs
- 16 output contacts
- the type of the contacts (NC or NO) can be selected individually for
each contacts when ordering
- versions for 19" rack cabinet mounting or housed in relay case
(semi-flush mounting or hinged type)
Communication:
- 2x16 character LCD display for setting the functions, displaying messages
and reading event records
- on-line screen on external PC to make commissioning and testing easier
- external communication interface, can be set for RS 232 or for fibre
optic cable
- optional interface module with IEC 870 protocol for SCADA systems
- the set parameters can be saved and downloaded
- real time clock handling with the aid of RAM with battery, (which
can be synchronised via optical fibre cable connected to external PC,
to the SCADA system, or through an optical cable)
|
Working principle |
|
The DGSZV-EP device is a fully microprocessor based construction, the
functions and their versions are realised basically on software. The device
contains a 87C196 type 16 bit micro-controller. The program is stored
in the internal EPROM of the controller, the message text for the display
is stored in EPROM as well. The parameter setting is loaded in EEPROM.
Events are recorded in battery supplied RAM. The man-machine interface
consists of a keyboard with six push-buttons, above it the two row, 2
x 16 character LCD display, seven LEDs and two SW pushbuttons. With the
help of an external PC and communication software the handling of the
device is easier .
The analog current and voltage inputs ire connected via inductive internal
measuring transformers and low-pass filters to the multiplexer then to
the ND converter, where all current and voltage signals are sampled in
every 0,5 ms. The sampled values of the 16 bit AID converter are passed
via high speed CAN bus to the CPU. The central processor communicates
via parallel bus with the optocoupler inputs and with the relay drivers.
The protection contains a two stage definite time overcurrent protection
for all the three phases. The time delay of all stages can be set independently.
The two overcurrent stages contain RMS algorithm, the setting of the stages
is independent of each other .
The longitudinal differential protection function compares currents of
the own end and that of the far end, composed of the weighted (2x, 3x,
lx) three phase currents or composed of two weighted phase currents and
the zero sequence current (See Figure below), and decides if the fault
is inside the protected section and a trip command is issued, or the fault
is outside, when no trip command is generated. The algorithm compares
10 subsequent sampled values, then the comparison is repeated one period
later. If the evaluation shows twice difference, the trip command is generated.
The Id trip signal is composed of the vector difference of the single
phase currents of the two sides, the restraint current is the average
of the measured individual currents.
As because of the presence of the intermediate current transformers and
the connecting pilot cable, the saturation effects can be expected at
smaller currents, the f3 knee point of the characteristics must be set
lower, than that of the usual differential protection (see Figures). One
branch of the pilot cable is for the current proportional to the own current,
the second is for that of the opposite line side, the third branch is
for the sum of these currents (Id).
The pilot cable is supervised in the operating current range by a sensitive
differential function. The disabling (and the safety trip command if this
is set by parameters) is delayed, if there is no deviation, a drop delay
is set. The trip command can depend of voltage precondition, in this case
the protection submits warning signal only. The longitudinal distance protection
function, if voltage precondition is set, is blocked by the open signal
of the miniature circuit breakers in the voltage transformer's secondary
circuit.
The galvanic longitudinal differential protection contains intermediate
current transformers, and depending on the turns ratios of the mixing current
transformers, at the rated current 5 A and 1 A as well, the current in the
pilot cable is between 20 mA and 40 mA. One branch of the pilot cable is
for the current proportional to the own current, the second is for that
of the opposite line side, the third branch is for the sum of these currents
(Id). In case of load current, or in case of external faults this branch
has double current sum. This makes possible a quick and simple supervision. |
|
Technical data |
|
Rated secondary current, In
|
1 A or 5 A |
Rated secondary voltage, Un |
100 V or 200 V |
Rated frequency |
50 Hz or 60 Hz |
Overload capacity,
voltage circuits, thermal, continuous
current circuits, thermal, continuous
1 s |
2xUn/Ö3
4xIn
100xIn (In=1 A), 50xIn (In=5 A) |
Dynamic current limit |
100xIn |
Accuracy, digital overcurrent relay (over
50% In)
digital timers |
± 2%
± 3 ms (steps 10 ms)
± 12 ms (steps 1 s) |
Resetting ratio, overcurrent relays |
95% |
Number of output contacts |
12 pcs |
Output contact type (NC, NO) |
1 NC, 12 NO (as requested) |
Output contacts, electrical
data:
rated switching voltage
continuous load current
making current
DC breaking capability at 220 V,
at pure conductive load
at load of L/R = 40 ms
at load of L/R = 40 ms (optionally)
|
250 V
8 A
16 A
0,25 A
0,14 A
4 A |
Auxiliary DC voltage (same suplly unit)
voltage tolerance
|
220 V or 110 V
88 V to 310 V |
Permissible ambient temperature |
0o to 50o C |
Insulation test (IEC 255) |
2 kV, 50 Hz
5 kV, 1.2/50 µs |
Disturbance test (IEC 255) |
2.5 kV, 1 MHz |
Electrostatic discharge (ESD; IEC 801-2) |
8 kV |
Burst test, (IEC 801-4) |
2 kV |
Setting ranges: |
Basic setting (Id>f1*Ibe)(f1) |
10-200%, step 2% |
Slope of section 2 (Id>f2*Is)(f2) |
40-80%, step 2% |
Slope of section 3 (Id>2Is - f3*Ibe)(f3) |
50-2000%, step 10% |
Voltage condition, U>/Un |
20-100%, step 5% |
The tertiary rated current at the own side (Iset(own)) |
0,2 A, fixed |
The tertiary rated current at the opposite side (Iset(opp)) |
0,2 A, fixed |
Delay of signalling cable error |
0-64000 ms, step 10 ms |
Low set overcurrent funtcion, I>/In(AV) |
50-2500%, step 5% |
High set overcurrent funtcion, I>>/In(AV) |
50-2500%, step 5% |
CT rated primary current, In(AV) |
50-2500 A, step 25 A |
External communication channel |
RS 232/fibre optic cable |
Communication rate (BaudRate) |
150 do 19200, step:2x |
Optical cable operating mode |
radial or loop |
Daily automatic self-check time |
23 h 59 min, step 1 min |
Automatic self-check, block |
to 60 min |
|
|
Design, size |
|
An EuroProt device is always rack mounted, it has two design forms. One
of the form is suitable to be mounted into standard 19" cabinet frame,
this form is also suitable to be mounted directly to a relay panel with
flash mounted form. The other form is a relay panel mounted device with
raised-hinged form.
Design
|
Width
|
Height
|
Depth
|
Rack mounting
|
483 mm
|
132,5 mm
|
201 mm
|
Panel mounting
|
490 mm
|
250 mm
|
250 mm
|
Weight 8 kg. |
|
Options |
|
- digital disturbance recorder (see separate information sheet)
- SCADA connection (see EuroProt system information sheet)
- output relays with 4 A breaking capability
|
|
Information required with order |
|
- Protection type [DGSZV-EP]
- Output relay contact type [NC or NO, if deviates from the Technical
Data]
- Rated current [1 A, 5 A]
- Rated voltage [100 V, 200 V]
- Protection case type [19" cabinet frame mounted device, or panel
mounted device]
- Options if needed
|
|
|